How do I charge certain deep cycle 6-volt and 12-volt batteries?

Charging Recommendation for all Deep Cycle Batteries whose part number start with the letter "U" (this includes the following battery part numbers: U1800, U2000; U2200, U2300, U2400, U2500, U3050, U3050HC, UL-16, UL-16HC, U1450, U1850, U1850HC; U8VGC, U8VGCHC, USRM8V19, USRM8V-21, USRM8V-24, USRM8V-27; USRM8V-26, U-BIG-JOE; USRM-16TF, USRM-8D)

Nominal Battery Voltage Charging Current Bulk Charge Voltage (2.4 VPC) Absorption Voltage (2.58 VPC) Absorption Time in Hours Float Voltage (2.2 VPC) Equalization Voltage (2.6 VPC) Equalization Time in Hours
6 Volts (3 cells) C/10 7.2 7.75 2 to 4 6.6 7.8 2
8 Volts (4 cells) C/10 9.6 10.33 2 to 4 8.8 10.4 2
12 Volts (6 cells) C/10 14.4 15.5 2 to 4 13.2 15.6 2
24 Volts (12 cells) C/10 28.8 30.96 2 to 4 26.4 31.2 2
36 Volts (18 cells) C/10 43.2 46.44 2 to 4 39.6 46.8 2
48 Volts (24 cells) C/10 57.6 61.92 2 to 4 52.8 62.4 2

 
Need to determine the volts and amp-hours for your battery? See below
1. C = 20 hour capacity in Amp-hours
2. Float condition is for long term storage (several weeks).
3. Equalize every 4 to 8 weeks and always after a normal charge.
4. Be sure to leave the vent caps on your battery (or batteries) while charging them.

Charging recommendation for the UAGM8D (rated at 250 AH at the 20-hour rate):

Voltage of the Battery System

Charging Current

Bulk Charge Voltage     

Absorption Voltage  

Absorption Time in Hours

Float Voltage   

Equalization Voltage       

Equalization Time in Hours

12

C/10

14.4

14.4

2 to 4

13.2

14.4

2


Notes
1. C = 20 hour capacity in Amp-hours
2. Float condition is for long term storage (several weeks).
3. Equalize every 4 to 8 weeks and always after a normal charge.


Charging recommendations for 6-volt deep cycle batteries. GC2-XHD, GC2-HD, GC2-RD

Nominal Battery Voltage

Charging Current

Bulk Charge Voltage (2.41 VPC)

Absorption Voltage (2.55 VPC)

Absorption Time in Hours

Float Voltage (2.23 VPC)

Equalization Voltage (2.6 VPC)

Equalization Time in Hours

6 Volt (3 cells)

C / 10

7.23

7.65

2 to 4

6.7

7.8

2

8 Volt (4 cells)

C / 10

9.64

10.2

2 to 4

8.92

10.4

2

12 Volt (6 cells)

C / 10

14.46

15.3

2 to 4

13.4

15.6

2

24 Volt (12 cells)

C / 10

28.92

30.6

2 to 4

26.8

31.2

2

36 Volts (18 cells)

C / 10

43.38

45.9

2 to 4

40.2

46.8

2

48 Volts (24 cells)

C / 10

57.84

61.2

2 to 4

53.5

62.4

2



Notes: 1. All charging voltages shown above are for 80 degrees F. For every 10 degrees above 80 F reduce voltage by 0.028 VPC. For every 10 degrees below 80 F increase the voltage by 0.028 VPC.
2. VPC = Voltage Per Cell
3. Charging current; C = The amp hour (Ah) capacity rated at the 20 hour rate.
4. Float condition is for long term storage / (several weeks) inactivity. 5. Equalize every 4 to 8 weeks or when the difference in specific gravity readings vary by 0.020 points or more and always after a normal charge.

Other Charging Notes/Tips/ Definitions: Temperature Compensation: Increase voltage by .028 volts per cell for every 10 degrees below 80 F. Decrease voltage by .028 volts per cell for every 10 degrees above 80F. Typical phases on multi-stage chargers: Bulk: Initial phase where the voltage builds and the most current is provided to the battery. This is typically where the maximum current that the charger is capable of providing is supplied to the battery. i.e. A 10 amp charger will provide at or near 10 amps during this phase. Absorption: The phase where the voltage set point is held constant. Current will decrease gradually during this point as the battery internal resistance comes up. Float:

The maintenance or finishing phase of the charging cycle. Voltage is set at a minimum during this phase (usually 13.0c-13.5v) and current drops significantly. The battery should be nearly complete by the time this phase is reached. An anti sulfation stage may be added where voltage spikes to high levels for very brief time periods for a set amount of time determined by the charger manufacturer, to convert the battery active material back to it's original state. Badly sulfated batteries will not usually respond to this charging regime and will need to be replaced.

Would you like to...

Print this page Print this page

Email this page Email this page

Post a comment Post a comment

Subscribe me

Add to favorites Add to favorites

Remove Highlighting Remove Highlighting

Edit this Question

User Opinions (1711 votes)

89% thumbs up 10% thumbs down

How would you rate this answer?

Helpful
Not helpful
Thank you for rating this answer.

Related Questions

No related questions were found.

Attachments

No attachments were found.